Proper maintenance

Proper maintenance will keep a transmitter’s cooling system clean, and this, in turn, will lead to a longer life for your IOTs. The first thing that should be done is to have the coolant tested at least every year. The coolant manufacturers will usually test their own glycol, for a fee, and report whether it needs to be changed out. You can also use an outside lab to test your coolant; just be sure they are qualified to do this type of testing. Dow Chemical will do an analysts of your glycol, but their reports tend to be limited in scope, more of a pass/no pass, whereas an outside laboratory can give you a much more detailed report. In fact, a good way to compare the results would be to have an analysis done as soon as the transmitter is installed and use that report for comparison.

Figure 5

Figure 5

Some of these detailed analyses list levels of inhibitors, but without a reference, it’s hard to tell if it’s within limits. This is where consulting with the tube manufacturer comes in handy. (See Figures 4a and 4b.)

The main criteria for any glycol mix are the pH level, conductivity, oxidation and the level of corrosion inhibitors. The presence of glycolate is an indicator that the glycol is breaking down.

A simple test that any engineer can perform is a pH test using an inexpensive pH meter. After drawing a clean sample, you can read the pH of your coolant. It should be within the range of eight to 10.5. (See Figure 5.) Another check you can perform is to make sure the level in the reservoir tank is high enough that the returning coolant is below the level of the tank. If the returning coolant is above the tank level, then the coolant will be aerated, which contributes to the corrosion process.

Figure 6

Figure 6
Click to enlarge

Once you have determined that the coolant is getting close to the limits for pH and/or the levels of inhibitors, it’s time to change out the coolant. In the past, you could purchase additives to bring these levels back within range, but many believe that the cost of changing the coolant is far smaller than the risk of a damaged IOT. It is believed that the life span of glycol in a typical transmitter is about five years, but no manufacturer recommends that you wait that long. As long as the coolant is regularly tested, it will be apparent when it’s time to change it. (See Figures 6 and 7.)

At the minimum, the coolant should be drained and refilled, but it is always better to do one flush with distilled water and then refill the system if there were no indications of corrosion. But as mentioned above, if the analysis shows signs of corrosion, then a full cleaning should be performed before refilling the system.

Figure 7

Figure 7
Click to enlarge

Acknowledgments
Vijay Patel, Mark Strohecker and Neil O’Sullivan of e2v contributed to this tutorial.

Next time

The next “Transition to Digital” tutorial will cover multidepressed collector IOT cooling.




Want to use this article?
Click here for options!
Get Copyright Clearance

Share this article

blog comments powered by Disqus

 

Current Issue

Online captioning compliance

May 2012

The FCC has issued captioning requirements for all online video. Learn how to meet the requirements of the new rules and how to automate the technical process.

Read More articles...

Related Newsletter

Transition to Digital
A twice per month tutorial on digital technology.

Confused about the terminology in an article? Find definitions of common terms and abbreviations in Broadcast Engineering's Glossary.

 


Video Compression, Editing and Displays

Video Compression, Editing and Displays

Video compression, editing and displays is an in-depth tutorial on MPEG compression technology, editing MPEG content and evaluating color video monitors written by long-time video expert, trainer and writer Steve Mullen, Ph. D.

File Based Technology and Workflow

File Based Technology and Workflow

File-based technologies have replaced video tape methods for a majority of production and broadcast operations. The worlds of AV and IT are coalescing to create new methods and workflows for media

Sound Off Podcasts

 

Broadcast Engineering Digital Reference Guide

Browse Back Issues

Back to Top